Healthcare
Control the Transfer of Airborne Contaminants
The use of air pressure stabilisers within isolation rooms, operating theatres and clean environments provides a well-established solution for contamination control.


The use of air pressure stabilisers within isolation rooms, operating theatres and clean environments provides a well-established solution for contamination control.
Operating Theatre Suites designed in accordance with HTM 03-01 employ cascade ventilation systems and require the use of Air Pressure Stabilisers to accurately control and maintain differential pressures between adjoining rooms. Cascade ventilation ensures the flow of air moves one way only, cascading from the cleanest (most sterile) area within a suite, down into the various rooms, and finally out to the assigned dirty area. When the doors between adjoining rooms are closed, Apreco’s VARI-centric Air Pressure Stabiliser opens to allow the air to cascade through to the next area.
When the door is open, Apreco’s VARI-centric Air Pressure Stabiliser closes pushing the air through the open door creating an invisible barrier of air through the doorway; stopping unwanted particles from passing through into the next room. As the airflow is constantly maintained, any unwanted particles (if present) will move down the system making their way safely away from the patients and staff.
Air Pressure StabilisersWhen following the guidelines of HBN4 Supplement 1: Isolation facilities; Apreco’s VARI-centric Air Pressure Stabilisers are utilised to accurately maintain the positive pressure ventilated lobby (PPVL) room ensuring that air from the corridor does not enter the isolation room and that air from the room does not escape into the corridor.
This simple but effective design enables the suite to be used for both source and protective isolation without the need for switchable ventilation or special training for staff.
Importantly it also provides safe isolation for those patients whose exact condition is unknown. To complement the Air Pressure Stabilisers Apreco can also offer Air Pressure Transmitters (APT) / Gauges (APG) to display the room pressures.
Air Pressure StabilisersApreco’s VARI-centric Air Pressure Stabilisers are an ideal way of providing the pressure differential between areas within the SSD facility.
The IAP room is Class 8 classified as detailed in BS EN ISO 14644. It should have 20 air changes per hour with a pressure differential of not less than 10Pa between the IAP room and adjoining rooms. HBN 13 refers to pressure relief dampers to move air to adjacent areas.
However, Apreco would not offer pressure relief dampers/vents for this application as they are not suitable due to their linear flow/differential characteristic which, is more suitable to pressure relief applications.
Air Pressure StabilisersThe VARI-Centric® range of Air Pressure Stabilisers featuring the Easi-release™ blade system are continuously safe-guarding and protecting hospital patients and staff from the transfer of airborne contamination around the globe.
View Products